한국농촌건축학회논문집, Vol.22 no.1 (2020)
pp.1~12

DOI : 10.14577/kirua.2020.22.1.1

- 전주시 공동주택 지하주차장의 실내환경 개선에 관한 연구 -

정재연

(전북대학교 주거환경학과 박사과정)

정인수

(전북대학교 주거환경학과 교수, ph.D)

포위

(전북대학교 주거환경학과 석사과정)

The main purpose of the research is to prevent residents who are using underground parking lot from being exposed to pollusion, and to allow them to enjoy clean indoor environment. The study subject for the research are underground parking lots in 20 different apartments, 4 of them were constructed before 2000, 10 were constructed from 2000-2010, and the rest were constructed after 2010. By analyzing the air quality in these underground parking lots, we found out that O3, NO2, CO, PM10, Radon in all parking lots were not excessive compared to the standard limit. TVOC rate was measured with the value in between 312 ~ 2,137μg/m3, with CO2 value in between 193~1,824 ppm, and HCHO with the value in between 0.01~1.52ppm. The lightning system in underground parking lots in apartments constructed before 2000 were using manual light control system, while automatic light control system was used in all apartments constructed after 2000, and the brightness of parking lots in apartments constructed before 2000 was quite low. The apartments constructed after 2000 are performing cleaning and ventilation due to management agreement, while the apartments constructed before 2000 are not performing regular cleaning and there was no mechanical ventilation system installed. The difference of indoor air quality was significant seasonally, daily, and yearly (year of construction), while illuminance was significantly different yearly.
  지하주차장,실내 환경,조명,자동제어,수동제어,청소,환기